The most common fault phenomenon and troubleshooting method of vortex flowmeter

The vortex flowmeter produces the following causes: 1. The quality of the vortex street is not good; 2. The vortex street type is incorrect; 3. The vortex flowmeter is improperly installed; 4. The vortex flowmeter has interference signals on the spot; Vortex did not pay attention to maintenance.

Vortex flowmeter failure Phenomenon : There is flow in the pipeline, but the flow is shown as 0
Troubleshooting method: 1. Make sure that there is indeed flow in the pipe and is greater than the lower limit of measurable flow.
2. Check if the flow cutoff setting is too large.
3. If the pipe flow is normal, adjust according to the method on the first page (the flowmeter is zeroed on the field), and it will become output and display, indicating that the work is almost normal.
4. If there is still no output, the traffic still shows 0, and the cumulative amount does not change, indicating that the circuit board has a problem and should be considered for replacement.
5. If the cumulative value increases regularly in the fourth test, the problem lies with the sensor head.
6. Judging the sensor head is good or bad. Remove the two leads of the sensor head from the “S, T” terminals at the bottom of the rear circuit board, measure the resistance of the two lead wires of the sensor head with a multimeter, and the resistance of the two lead wires of the sensor head to the housing, respectively, should be greater than 2 MΩ. , otherwise need to replace the sensor head. If the sensor head is normal, then the rear circuit board will have to be replaced.

Vortex flowmeter failure phenomenon: There is no flow in the pipeline, but the display value is changing. Troubleshooting method: 1. Check if the instrument installation position is excessively vibrating. If the vibration is large, refer to page 10, 1 and 2 for shock absorption. .
2. Turn the 6 (potentiometer) in Figure 10 clockwise to the magnification until the amplifier just has no output and zero the flow.

Vortex flowmeter failure phenomenon: LCD display shows a rapid increase in the rate of failure Troubleshooting: shutdown, restart. If it does not work, repeat it several times.
Vortex Flow Meter Failure Symptom: The LCD display is dim. Troubleshooting: Shutdown and restart. If not, notify the factory.

Vortex flowmeter failure phenomenon; LCD display alternately bright or all black, the current output also jumps between the maximum and minimum. Troubleshooting: Shutdown, restart. If not, notify the factory.

Vortex flowmeters have been developed over the years and their products have become more sophisticated, playing an important role in many steam trade measurements.

2inch Slackline Kits Trickline

The TRICK LINE offers dynamic movement and bounce for tricklining, the branch of the sport that goes beyond walking by adding jumps, spins and rotations. Featuring trampoline-style webbing with rubber grip and a backup line system, this kit is ideal for intermediate users and beginner tricks.Thick felt wraps with Velcro closures are included to protect the trees and the Slackline from abrasion.An easy-to-use backup line is included as an added safety measure. This is an important precaution for tricklining which amplifies force on the line.

Slackline Kits Trickline,Slack Rope Long Line,Slackline Industries Baseline,Slackline Yoga,Slackline Rope,Slackline 50M

WINNERLIFTING SAFETY EQUIPMENT CO., LTD. , https://www.ratchetstrapfactory.com