This is a good machine for making twisted paper handle. It pastes the twisted Paper Rope and paper strap together and cut off them for separate handles. It is running stably and fast with hot melt glue application. The handle size can be customized according to customers` request and one machine can make several different handle sizes.
handle length:190mm,152, 114mm
paper strap width:30/40mm
speed:10000 pairs per hour
Paper rope dia: 3-4mm
power:7.8kw
machine weight:1500kg
machine dimension:4200*1300*1500mm
Hot glue pasting system
the sizes can be customized according to the customers' actual needs.
Paper Handle, Paper Twisted Paper Handle Machine, Paper Handle Machine, Paper Handle Machinery. Paper Handle Making Machine DongGuan FeiYang Packaging Machinery Equipment Co., Ltd , https://www.feiyang-machinerys.com Transformer capacity calculation - Temporary elimination method when the transformer cannot be stopped: External lead wires, when the fault current is large, can temporarily open the line operation. However, monitoring must be strengthened and the cores appear to have a floating potential after the fault point disappears. Multi-point faults are unstable, and a slip wire resistance can be connected in the working wiring to make the current limit 1A or less. Slip line resistance selection is to divide the normal operating wiring open test voltage by the line current.
Transformer capacity calculation method:
1. Calculate the capacity according to the load factor βM at which the efficiency of the transformer is highest.
After the calculation load of the building is determined, the total installed capacity of the distribution transformer is: S=Pjs/βb×cosφ2(KVA) (1)
In the formula, Pjs  - the active calculation load KW of the building;
Cosφ2 - the average power factor after compensation, not less than 0.9;
Βb - transformer load factor. 
Therefore, the final determination of the transformer capacity lies in the selected transformer load factor βb. 
The highest efficiency is βb=βM=Po/PKH(2)
In the formula Po, the no-load loss of the transformer;
PKH  - short circuit loss of the transformer. 
However, in high-rise buildings, equipment rooms are mostly located in the basement. To meet the requirements of fire protection, general information about distribution transformers is available at: Power Transmission and Distribution Equipment
With dry or epoxy cast transformers, Table 1 is the best load rate of domestic SGL power transformers. 
The best load rate of domestic SGL power transformers
Capacity (KVA) 500 630 800 1000 1250 1600
No-load loss (watts) 1850 2100 2400 2800 3350 3950
Load loss (Watts) 4850 5650 7500 9200 11000 13300 Source: http://tede. Cn
Loss ratio α2: 2.62 2.69 3.13 3.20 3.28 3.37
Optimal load rate βm% 61.8 61.0 56.6 55.2 55.2 54.5